Wanem samting em i 'partial discharge' insait long wanpela pawa trensfoma, na bilong wanem em i denja?

 May 14, 2026

 Larim wanpela toksave

 

Wanem samting em 'partial discharge', na olsem wanem dispela i save mekim 'transformer' i bagarap?

 

'Partial discharge' (PD) em i wanpela 'localized electrical breakdown' we i no inap long pasim olgeta 'insulation'. Em i save kamap long ol spes, ol 'gas bubble', ol 'oil gap', o arere long ol 'insulation surface' we 'local electric field' i winim strong bilong 'dielectric'.

Fisiks bilong PD:

• Elektron bom - i brukim ol sen bilong polima insait long pepa/oil.

• Lokalisait hiting - inap long sampela handet digri, na mekim insulesen i kamap kabon.

• Kemikel bagarap - i save kamapim H2, C2H2, CO (DGA i ken painim).

• Asid fomesen - selulosa bagarap i save mekim man i kamap lapun hariap.

Steij

Ektiviti

Rot bilong painimaut

Taim bilong feil

Stat

Micro-voids i save kamaut sampela taim

UHF / HFCT (sensitive)

Ol yia

Divelopmen

Discharge i kamap stebol na i save kamap planti taim

PD monitoring + DGA

Ol mun

Akseleresen

Ol fom bilong bihainim ol diwai

DGA (H2, C2H2 i go antap) + PD i wok long go antap

Ol wik

Bipo-feil

Bikpela sik PD, klostu bagarap

Planti alam

Ol de i go long ol aua

Bilong wanem PD em i denja:

• Wanpela transfoma inap long wok inap planti mun wantaim PD i wok pastaim long em i bagarap.

• Bagarap i bikpela na i no inap long senis - pepa we i gat kabon i no inap long stretim gen.

• ~30-50% bilong ol in-sevis trensfoma i bagarap i kamap long PD (CIGRE) we ol i no painim aut.

Bikpela samting:

PD testing em i wanpela TRENDING tul. Bikpela o 'repetition rate' i go antap na i nidim wok painimaut hariap.

Askim wok painimaut
Askim wok painimaut