Wanem samting em 'partial discharge', na olsem wanem dispela i save mekim 'transformer' i bagarap?
'Partial discharge' (PD) em i wanpela 'localized electrical breakdown' we i no inap long pasim olgeta 'insulation'. Em i save kamap long ol spes, ol 'gas bubble', ol 'oil gap', o arere long ol 'insulation surface' we 'local electric field' i winim strong bilong 'dielectric'.
Fisiks bilong PD:
• Elektron bom - i brukim ol sen bilong polima insait long pepa/oil.
• Lokalisait hiting - inap long sampela handet digri, na mekim insulesen i kamap kabon.
• Kemikel bagarap - i save kamapim H2, C2H2, CO (DGA i ken painim).
• Asid fomesen - selulosa bagarap i save mekim man i kamap lapun hariap.
|
Steij |
Ektiviti |
Rot bilong painimaut |
Taim bilong feil |
|
Stat |
Micro-voids i save kamaut sampela taim |
UHF / HFCT (sensitive) |
Ol yia |
|
Divelopmen |
Discharge i kamap stebol na i save kamap planti taim |
PD monitoring + DGA |
Ol mun |
|
Akseleresen |
Ol fom bilong bihainim ol diwai |
DGA (H2, C2H2 i go antap) + PD i wok long go antap |
Ol wik |
|
Bipo-feil |
Bikpela sik PD, klostu bagarap |
Planti alam |
Ol de i go long ol aua |
Bilong wanem PD em i denja:
• Wanpela transfoma inap long wok inap planti mun wantaim PD i wok pastaim long em i bagarap.
• Bagarap i bikpela na i no inap long senis - pepa we i gat kabon i no inap long stretim gen.
• ~30-50% bilong ol in-sevis trensfoma i bagarap i kamap long PD (CIGRE) we ol i no painim aut.
Bikpela samting:
PD testing em i wanpela TRENDING tul. Bikpela o 'repetition rate' i go antap na i nidim wok painimaut hariap.