Test Voltage Selection — wanem DC voltage mi mas putim long tes bilong kebol?

 Jun 16, 2026

 Larim wanpela toksave

 

Q: Megger bilong mi i gat 500V, 1000V, 2500V, 5000V, na 10kV. Mi mas makim wanem bilong LV, MV, na HV?

 

A: Sapos yu putim liklik 'voltage' tumas dispela i no inap givim hevi long 'insulation'. Planti tumas inap long kamapim wanpela bagarap -tru. Bihainim tebol we i wankain.

Standet DC Test Voltej Seleksen:

Kebol Reit Voltej (U0/U)Insulesen KlasVoltej bilong DC Test we ol i tok orait long enSefti Limit (Maks)
Low Voltage (LV) < 0.6/1 kVLow Voltage500V i go long 1000V DC1000V DC
Namel Voltej (MV) 6/10 i go long 20/35 kVNamel Voltej2500V o 5000V DC5000V DC
Hai Voltej (HV) 66 i go long 220 kV+Hai Voltej5000V o 10,000V DC10,000V DC

Bilong wanem yusim DC long IR? Wanpela DC saplai i no save pulim 'capacitive charging current' bihain long ol namba wan seken, na dispela i larim ol long skelim liklik 'resistive leakage current' (micro-amps) we i ron insait long 'insulation'.

Askim wok painimaut