Q: Sapos 'purity' i go daun long 95% bikos win i kam insait, bai GIS i wok yet?
A: Em bai stap strong, tasol ol 'safety margins' ('arc quenching' na 'cooling') i go daun tru.
Ol hevi bilong liklik klinpela:
❶ Daunim Arc Quenching: Win i 100x nogut moa long SF6 long stopim ol arc. CB i no inap long stopim toktok.
❷ Heat Dissipation: Kontaminesen i save senisim 'gas density' na 'cooling ability', na dispela i save mekim em i hat tumas.
Ol standet (IEC 60480):
• Nupela Ges: Bikpela o wankain olsem 99.9%.
• Ges i ron: I mas > 97%. Aninit long 95% i nidim 'reclamation'.
Hau bai yumi inap long tanim SO2 na HF level?
Q: Analyzer i soim 5 ppm bilong SO2. Nomal risal o intanel asua?
A: SO2 em i "Smoke Alarm" bilong 'internal arcing'. Tanim olsem:
|
SO2 Level |
Intapretesen |
Eksen |
|
< 1 ppm |
Nomal operesen. |
Monitoring oltaim. |
|
1 – 5 ppm |
Liklik PD o bikpela senis. |
Sotim taim bilong tes. |
|
5 – 10 ppm |
Wanpela bikpela bagarap i kamap. |
Mekim wok painimaut long yusim UHF/Acoustic PD. |
|
>10 ppm |
BIKPELA bagarap insait long bodi. |
Sekim/klinim hariap. |
Tip bilong saveman: Sapos SO2 na HF i antap, orait yu gat wanpela ACTIVE defect we i save kamapim asid nau.