Hau long skelim SR sistem kapasiti bilong wanpela kebol o GIS tes?

 May 26, 2026

 Larim wanpela toksave

 

Q: Mi mas traim wanpela 220 kV kebol, 8 km longpela. Mi nidim wanem SR reiting?

 

A: 7-step sising prosedur: painimaut ol samting bilong tes → skelim C → skelim L → skelim f_res → sekim ol reiting → mekim gen → pinisim.

Step-long-step - 220 kV kebol, 8 km:

1. IEC 60840: V_test=2.0 × 127 kV=254 kV. Longpela bilong en 60 minit.

2. C ≈ 8 km × 0.2 μF/km=1.6 μF.

3. Tingim 3× 100 kV/2 A riaksen i stap wankain: L=26.7 H, f=24.4 Hz.

4. Karent long 254 kV: I=V × 2πf × C=6.9 A. Tasol 3×2A → 6A olgeta → I NO OK.

5. Apgredim i go long 3× 100 kV/4 A reakta: olgeta I=12 A → OK. P_in=254×6.9/35=50 kW.

6. Hevi bilong olgeta: 3×450 kg + 200 + 150 + 100=~1,800 kg.

 

Samari bilong sais bilong ol komon senario:

Senario

V_test (kV)

C (μF)

f (Hz)

Sistem we ol i rekomendim

33 kV kebol, 3 km

48

0.6

45

60 kV/2A ×1, 5 kW

110 kV kebol, 5 km

160

1.0

24

200 kV/4A ×2, 20 kW

220 kV kebol, 8 km

254

1.6

24

300 kV/4A ×3, 50 kW

400 kV kebol, 5 km

330

1.0

48

400 kV/2A ×2, 25 kW

GIS 245 kV, 10 bei

230

0.05

80

300 kV/1A ×2, 5 kW

Jenereta 100 MVA

28

2.5

45

30 kV/5A, 10 kW

 

Ol bikpela toksave:

• +20% mak long 'reactor voltage rating. +30% mak long 'current rating'.

• Sapos P_in > 100 kW, tingim 'sectional testing' (planti standet i orait long en).

• Tru tru Q i ken i stap daunbilo long mak ol i ting bai kamap - gutpela plening i save abrusim ol hevi long fil.

Askim wok painimaut